kraftwerk - Mephisto BHKW G50

G50

Natural gasAsynchronous

Maximum output in minimum space.

Technical data

Mephisto G50

TypeMephisto G50 A NGGeneratorAsynchronous generatorFuelNatural gas

Net output (adjustable)

Electric, net20 to 50 kWElectric, gross50,6 kWThermal63 to 100,7 kWGas79,5 to 144,9 kWHi

Net efficiency Electric

Electric, effective34,5 %Electric, ISO 304636,2 %Thermal, effective69,5 % (tReturn = 35 °C)Overall, effective104,0 % (tReturn = 35 °C)

General

Energy efficiency classA++Seasonal space heating energy efficiency 153 %CHP coefficient0,50Primary energy factor(fPE,WV as per DIN SPEC 4701-10/A1:2016-05) 0,19Primary energy saving32,4 % - The high-efficiency criterion specified in EU Directive 2012/27/EU for CHP systems is met.FuelNatural gas

Gas connection

Gas connection rating144,9 kWHi = 160,7 kWHSGas connection pressure20-100 mbarGas flow pressure≥ 10 mbarMating dimensionDN 32 (3/4″ male thread)

Heating connection

Heating circuit minimum pressure1,5 barPermitted operating pressuremax. 6,0 barFlow temperaturemax. 90 °CReturn temperaturemax. 70 °CMating dimension1 1/2“ male threadDesign flow rate4,41 m³/hResidual head for net output6,1 mWSWith 40 K spread:Design flow rate: 2,21 m³/h
Residual head for net output: 10,3 mWS

Electrical connection

  • Pre-fuse NH00 100 A gL (gG) or SLS E-100 A
  • Supply line H07RN-F 5 x 35 mm2, up to 50 m in length for installation types B to G; 35 mm2 for all installation types

Plate heat exchanger

Soldered stainless steel compact heat exchanger for separating the heating system from the CHP engine water circuit

Pollutant emissions

Mephisto G50 comes 50% below the German regulation emission limit

Combustion intake air

Space-air-dependent operating mode

Flue gas connection

  • Flue gas conduit D110, fire resistance class B1 plastic pipe made of PP, permitted as a flue gas conduit for condensing heat generators with flue gas temperature up to 120 °C
  • Flue gas temperature limited to max. 90 °C on thermostat
  • Safety thermal cut-out set to 100 °C
  • Recommended flue gas counter-pressure: 500 Pa; maximum flue gas counter pressure 800 Pa
  • Flue gas flow rate: 161 m3/h i.N. in normal state is equivalent to 208 m3/h at TFlue gas = 80 °C
  • Maximum condensate quantity: 22 l/h

Flue gas heat exchanger

  • Thermodynamically optimised cast aluminium-silicon heat exchanger
  • Integrated catalytic converter

Utilisation of calorific value

  • The flue gas temperature is a maximum of 15 K above the corresponding return temperature
  • Calorific value used at a return temperature of about 55 °C and above

Engine

  • industrial gas engine
  • Model: MAG 49.4 S 313/HMG 434 S 133
  • 4-cylinder Otto engine, water-cooled
  • Displacement: 4.900 cm³

Coupling

Maintenance-free, plug-in, flexible metal/plastic coupling to compensate for radial, axial and angular misalignment

Generator

  • Four-pole asynchronous machine for parallel operation on the public grid
  • Manufacturer: Weier GmbH
  • Model: DASGM 250/L 4 water-cooled
  • 3 × 400 V, 50 Hz
  • Anlaufstrom: 52 A (FU serienmäßig)
  • Rated current: 94 A
  • cos φ: 0,86 (inductive)
  • Rated power: 56 kW
  • Rated speed: 1.514 min-1

Compensation

Due to the requirements in German code of practice VDE-AR-N 4105:2018-11, operating own generating systems without reactive power compensation is only permitted in exceptional cases. A cos cos φ of 0.95 is achieved with the standard fixed compensation.

Controller

  • Industrial computer with powerful MPC555 microcontroller, 32-bit power PC with FPU
  • Fully automatic operating control
  • Remote monitoring/operation via LAN or optional mobile data connection
  • Interfaces to higher-level DDC controls: digital and analogue inputs and outputs; optional CAN bus, RK512, Modbus, LON bus, Profibus DP, BACnet/IP, IEC 104, Profinet

Housing

  • Sturdy, easily removable, frameless full thermoacoustic enclosure
  • Machine unit on four Asonator steel springs
  • Optional base on two vibration dampers to isolate noise

Noise emissions

  • Mean sound pressure level at 1 m distance ≤ 60,0 dB (A) as per DIN 45635-11
  • Mean sound pressure level (standard equipment) at 1 m distance (45°) to chimney outlet ≤ 51,2 dB (A) as per DIN 45635-11

Third octave band spectra isolation can be provided on request

Dimensions

L × W × H in mm: 2.235 × 1.020 × 1.930 mit Schaltschrank.

Required space

L × W × H in mm: 4.500 × 2.000 × 2.100, without sound insulation base. Height of sound insulation base: 250 mm.

Installation and base plans will be provided on request

Operating weight

1.850 kg

Delivery

  • Machine unit, self-supporting: 1.640 mm × 785 mm, 1.240 kg
  • Panelling with accessories on pallet: 2.000 mm × 1.200 mm, 590 kg

Product range

You will find all technical specifications for the supplied heat pumps and for our Mephisto combined heat and power units and the Direktor controller in the product range.

Download PDF

Accessories & equipment features

In addition to the standard scope of supply, we also offer a wide range of accessories to adapt the Mephisto CHP unit to your individual needs. Here you will find an overview of standard equipment and added options.

More information

Contact

Do you have any questions about the heat pumps we offer or would you like to submit a request for project planning? Send us a message.

Arrange a meeting now