kraftwerk - Mephisto BHKW G34

G34

Natural gasAsynchronous

The module between conventional performance classes.

Technical data

Mephisto G34

TypeMephisto G34 A NGGeneratorAsynchronous generatorFuelNatural gas

Net output (adjustable)

Electric, net14 to 34 kWElectric, gross34,5 kWThermal49 to 78 kWGas58 to 107,9 kWHi

Net efficiency Electric

Electric, effective31,5 %Electric, ISO 304633,1 %Thermal, effective72,3 % (tReturn = 35 °C)Overall, effective103,8 % (tReturn = 35 °C)

General

Energy efficiency classA++Seasonal space heating energy efficiency 149 %CHP coefficient0,44Primary energy factor(fPE,WV as per DIN SPEC 4701-10/A1:2016-05) 0,30Primary energy saving30,93 % - The high-efficiency criterion specified in EU Directive 2012/27/EU for CHP systems is met.FuelNatural gas

Gas connection

Gas connection rating107,9 kWHi = 119,7 kWHSGas connection pressure20-100 mbarGas flow pressure≥ 10 mbarMating dimensionDN 25 (1″ male thread)

Heating connection

Heating circuit minimum pressure1,2 barPermitted operating pressuremax. 4,0 bar (pressures up to 6 bar on request)Flow temperaturemax. 90 °CReturn temperaturemax. 70 °CMating dimension1 1/4“ male threadDesign flow rate3,42 m³/hResidual head for net output5,0 mWSWith 40 K spread:Design flow rate: 1,71 m³/h
Residual head for net output: 8,9 mWS

Electrical connection

  • Pre-fuse NH00 50 A gL (gG) or SLS E-50 A
  • Zuleitung H07RN-F 5 x 25 mm² to 50 m Länge für die Verlegearten B to G

Plate heat exchanger

Soldered stainless steel compact heat exchanger for separating the heating system from the CHP engine water circuit

Pollutant emissions

Mephisto G34 comes 50% below the German regulation emission limit

Combustion intake air

Space-air-dependent operating mode

Flue gas connection

  • Flue gas conduit D110, fire resistance class B1 plastic pipe made of PP, permitted as a flue gas conduit for condensing heat generators with flue gas temperature up to 120 °C
  • Flue gas temperature limited to max. 90 °C on thermostat
  • Safety thermal cut-out set to 100 °C
  • Recommended flue gas counter-pressure: 500 Pa; maximum flue gas counter pressure 800 Pa
  • Flue gas flow rate: 117 mN³/h entspricht 151 m³/h bei TFlue gas = 80 °C
  • Maximum condensate quantity: 15 l/h

Flue gas heat exchanger

  • Thermodynamically optimised cast aluminium-silicon heat exchanger
  • Integrated catalytic converter

Utilisation of calorific value

  • The flue gas temperature is a maximum of 15 K above the corresponding return temperature
  • Calorific value used at a return temperature of about 55 °C and above

Engine

  • Perkins industrial gas engine
  • Model: 1004 Si
  • 4-cylinder Otto engine, water-cooled
  • Displacement: 4.000 cm³

Coupling

Maintenance-free, plug-in, flexible metal/plastic coupling to compensate for radial, axial and angular misalignment

Generator

  • Four-pole asynchronous machine for parallel operation on the public grid
  • Manufacturer: Weier GmbH
  • Model: DASGM 200/L 4 water-cooled
  • 3 × 400 V, 50 Hz
  • Start-up current: about 224 A
  • Rated current: 57,7 A
  • cos φ: 0,85 (inductive)
  • Rated power: 30 kW
  • Rated speed: 1.538 min-1

Compensation

Due to the requirements in German code of practice VDE-AR-N 4105:2018-11, operating own generating systems without reactive power compensation is only permitted in exceptional cases. A cos cos φ of 0.95 is achieved with the standard fixed compensation.

Controller

  • Industrial computer with powerful MPC555 microcontroller, 32-bit power PC with FPU
  • Fully automatic operating control
  • Remote monitoring/operation via LAN or optional mobile data connection
  • Interfaces to higher-level DDC controls: digital and analogue inputs and outputs; optional CAN bus, RK512, Modbus, LON bus, Profibus DP, BACnet/IP, IEC 104, Profinet

Housing

  • Sturdy, easily removable, frameless full thermoacoustic enclosure
  • Machine unit on four Asonator steel springs
  • Optional base on two vibration dampers to isolate noise

Noise emissions

  • Mean sound pressure level at 1 m distance ≤ 62,2 dB (A) as per DIN 45635-11
  • Mean sound pressure level (standard equipment) at 1 m distance (45°) to chimney outlet ≤ 48,3 dB (A) as per DIN 45635-11

Third octave band spectra isolation can be provided on request

Dimensions

L × W × H in mm: 1.800 x 1.040 x 1.300 Without electrical enclosure.
Height with electrical enclosure: 1.910 mm

Required space

L × W × H in mm: 3.800 × 2.100 × 2.280, without sound insulation base. Height of sound insulation base: 250 mm.

Installation and base plans will be provided on request

Operating weight

1.350 kg

Delivery

  • Machine unit, self-supporting: 1.600 mm × 800 mm. 930 kg
  • Panelling with accessories on pallet: 2.000 mm × 1.200 mm. 400 kg

Product range

You will find all technical specifications for the supplied heat pumps and for our Mephisto combined heat and power units and the Direktor controller in the product range.

Download PDF

Accessories & equipment features

In addition to the standard scope of supply, we also offer a wide range of accessories to adapt the Mephisto CHP unit to your individual needs. Here you will find an overview of standard equipment and added options.

More information

Contact

Do you have any questions about the heat pumps we offer or would you like to submit a request for project planning? Send us a message.

Arrange a meeting now